| |
 
Oxyvent
Tank Preliminary Tests
Fluids and Heat Transfer Laboratory,
Trinity College Dublin
Objective
The primary objective of the current study is to provide experimental
measurements that
confirm the claims that the a hot water heating system with an Oxyvent
tank system installed will provide as good if not better space/comfort
heating than conventional wet radiator systems. A conventional radiator
system operates with a pump that circulates water to several radiators
linked in a row with the radiator inlets attached to a common feed
pipe and the radiator exits plumbed to a common return line (see
Figure 1). With the boiler thermostat adjusted to a temperature which
is nominally
between 72 ºC to 85ºC, the system is ‘balanced’ by adjusting
a valve located at the radiator exit to a nearly closed position,
which virtually stagnates the flow of water within the radiator,
until the
temperature drop across the radiator is nominally 11ºC. The claim
here is that the Oxyvent tank can provide like space/comfort heating
with
a lower boiler set point (~63 ºC) (without having to balance the
system i.e. with the outlet valves on each radiator all fully open).
For the
former, the obvious benefit is less fuel usage. For the later point,
the benefits are envisaged to be (i) improved long term reliability
and maintenance of the system since anything that compromises the
balancing of the system will negatively influence the heating characteristics
and require re-balancing, (ii) since the volumetric flow of water
through each radiator is larger one would expect better heat spreading,
(iii) since the water is no longer nearly stagnant within the radiator
it is less likely for air to become trapped requiring bleeding and
(iv) each radiator along the line will have an inlet temperature that
is nearly identical so that the heat throughput is ‘selfbalancing’.

Figure 1: Conventional hydronic space heating system.
Experimental Facility
An experimental facility was commissioned in order to perform baseline
tests in a typical
balanced system as well as a system operating with the Oxyvent tank
in place. The facility, shown in Figures 2 and 3 consists of a conventional
boiler with diesel as the combustion fuel, an accumulator tank and
6 Quinn wet radiators. The inlet and outlet of each radiator was
fitted with thermocouples to monitor the temperature. A turbine flow
meter
was situated at the exit of the last radiator so that the net power
dissipater by radiator #6 (Rad #6) could be monitored. All of the
measurements were acquired by a computer fitted with a data acquisition
system. Measurements were taken every second for several hours. Further
to this, a thermal imaging camera was utilized to provide thermal
maps of the radiators to gauge the heat spreading.

Figure 2: Experimental facility

Figure 3: Oxyvent tank
Results and Discussion
Figure 4 shows the thermal images of radiator #4 and radiator #6
for a balanced system (no
Oxyvent tank: top images) and ‘self-balancing’ system
(with Oxyvent tank: bottom images).
From the images it is immediately apparent that the temperature distribution
of Rad #4 is
much more uniform for the case with the Oxyvent tank in place. This
is clear when one
considers that the difference between the Tmax and Tmin is 16.6ºC
for the balanced system with an inlet to outlet temperature difference
of 11.7 ºC and an average temperature of 63.6ºC. For the scenario
with the Oxyvent tank installed and the outlet valve of the radiator
fully open the difference between the Tmax and Tmin for Rad #4 is
only 8.8ºC with an inlet to outlet temperature difference of only
4 ºC and an average temperature of 60.1ºC. Since the average temperatures
are very close and buoyant natural convection is the primary restriction
to heat flow, it is likely that total power dissipated by Rad #4
will be comparable for both situations. The same general trend is
observed for Rad #6, the last radiator
in the system. However, one notices that compared with the balanced
system in which the water inlet temperature (Tmax) has dropped by
3 ºC from Rad #4 to Rad #6, the inlet temperature of Rad #6 is only
0.8 ºC less than Rad #4 which illustrates the self balancing nature
of the system with the Oxyvent tank installed.

Figure 4: Thermal images of radiator #4 and radiator
#6 for a balanced system (no Oxyvent tank) and ‘self-balancing’ system
(with Oxyvent tank)
This self-balancing is illustrated more clearly in Figure 5 where
the inlet temperature to the
very first radiator in the system (Rad #1) and the inlet to the very
last radiator of the system
(Rad #6) are plotted with time for an interval of approximately 16
minutes. What is
immediately apparent is that for the balanced system, without the
Oxyvent tank, there is a
substantial difference in TR1 and TR6, in particular during the heating
phase (following the
boiler on/off due to the thermostat). However, the Oxyvent inlet
temperatures for the
Oxyvent system are nearly identical and within the experimental uncertainty
of the
thermocouples. Secondly, it is clearly evident that there are massive
temperature swings for the balanced system with the temperatures
within the system following the ramp-up and falloff caused by the
boiler turning on and off. However, the Oxyvent tank
appears to
significantly dampen-out these large fluctuations, presumably by
increasing the thermal
inertia of the system prior to Rad #1. These fluctuations are dampened
even though the
frequency of switching of the boiler is not significantly different
between the two cases as
indicated by the exhaust gas temperature readings illustrated in
Figure 6.

Figure 5: Inlet temperatures to Rad #1 and Rad #6

Figure 6: Exhaust gas temperature in the flue
The total area traced under
the respective curves in Figure 6 is qualitatively indicative of
the amount of energy being consumed in the boiler by burning of the
fuel,
which is less for the Oxyvent system.
Figure 7 shows the power output of Rad #6 with time. Once again,
the balanced system is
very responsive with very large amplitude fluctuations in the power
output due to the rapidly
changing temperatures since the volumetric flow rate remains constant
(~1.4 LPM). With the Oxyvent tank in place the amplitude of the fluctuations
are reduced considerable due to the increased thermal inertia induced
by the system. What is most important here is that, over time, the
average power output, that being the thermal energy dissipated by
Rad #6 into the room, is about the same with a small 8.8 % measured
drop. However, this 8.8% is within the experimental uncertainty of
the measurement system and is likely not significant. In reality,
the tighter power control of the Oxyvent system would provide exceptionally
improved comfort since it would maintain the temperature of a room
at a much
more steady temperature compared with the balanced system.

Figure 7: Net power output of Rad #6
Conclusions
The preliminary tests which have been carried out tend to indicate
that the claims of the
Oxyvent system are apparently true with a lower operating temperature
required, less fuel
consumed, improved temperature uniformity of the radiators, a system
that is ‘self-balancing’ and improved comfort heating.
home • environment • about
us • news & reviews • certification • radiators
domestic hot water • underfloor
heating • boilers • installation • contact us
Site copyright
of Oxyvent © All rights reserved
Back to top
|
|